Detailed Product Description
Capacity | 30KVA | 40KVA | 50KVA | 60KVA | 80KVA | 90KVA | 100KVA | 120KVA | |||
Main input | voltage | 380V/400V Linear voltage | |||||||||
Phase | Three phase four wire | ||||||||||
P. F. | >0.99 | ||||||||||
Harmonic current (THDI | <3% | ||||||||||
Voltage range | +20%~-40% Linear rating drop Between -20%~-40% and 100%~50% | ||||||||||
Frequency range | 40~70Hz | ||||||||||
Bypass input | Input voltage | 380/400/415V linear voltage | |||||||||
Input voltage range | +20%~-50% | ||||||||||
Input Phase | Three phase four wire | ||||||||||
Frequency range | 40~70Hz | ||||||||||
Output | Stable voltage precision balanceable load | ±0.5% | |||||||||
Dynamic voltage in instantaneous change | ±2% 0~100% load change | ||||||||||
Voltage aberration linear load | THD<0.5% Phase voltage | ||||||||||
Voltage aberration Non-linear load | THD<5% Phase voltage | ||||||||||
P.F. | 0.8 lag | ||||||||||
Frequency track range | 50Hz±3Hz | ||||||||||
Frequency precision battery inverter | ±0.1% | ||||||||||
3 phase difference | 120±0.5° balanceable or un-balanceable load | ||||||||||
100% imbalance degree of un-balanceable load voltage | ±3% | ||||||||||
Frequency track speed | <1Hz/s | ||||||||||
Inverter overload capability | 105%<load<110%, transfer to bypass after 60minutes 111%<load<125%, transfer to bypass and output after 10±0.1mintes 125%<load< 150%, transfer to bypass and output after 1 minute | ||||||||||
Bypass overload capability | Run long time when 150% load Hold on 100ms when load>1000% | ||||||||||
System | System efficiency linear load | 91% | |||||||||
Battery inverter efficiency linear load | 91% | ||||||||||
Display | LCD+LED | ||||||||||
EMC/EMI | Conduction/ radiation | FCC Part 15, Class A | |||||||||
Harmonic current | IEC6 1000-3-12 | ||||||||||
Anti-jamming | EN 6 1000-4-2 .3.4..6.8.9.11 Level III , EN 6 1000-4-5 Level | ||||||||||
Safety requirement |
| ||||||||||
Noise ( 1m ) | 55dB | 55dB | 62dB | 62dB | 62dB | 64dB | 65dB | 65dB | |||
Insulated resistance | > 2M (500VDC) | ||||||||||
Defence level | IP20 | ||||||||||
Battery quantity | 40PCs /38~42 PCs (optional) x12V battery | ||||||||||
Installation | Dimension(mm) (LxWxH) | 700x800x1820 | 1000x800x1880 | ||||||||
N.W.(KGs) | 300 | 320 | 340 | 360 | 400 | 550 | 570 | 600 | |||
Measure(mm) (LxWxH) | 790x880x1980 | 1090x880x1980 |